GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester

GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is a high-precision instrument, which can be applied to measure electrical loss tangent and capacitance of all kinds of high voltage electrical equipment in power plants, substations, laboratory, etc.

Quantity:
  • GDGS
  • GOLD
  • 9030849000

GDGS 

Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester


Introduction:

  • GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester is an integrated structure, there is a dielectric loss test bridge, a variable frequency power supply, a step-up transformer and a SF6 high stability standard capacitor built-in;

  • It can also supply high voltage source for testing.

  • Frequency can be changed to 50Hz, 47.5Hz\52.5Hz、45Hz\55Hz, 60Hz, 57.5Hz\62.5Hz, 55Hz\65Hz; thus, it can avoid interference of power frequency;



Specifications:

No.

Item Name

GDGS Automatic Transformer Power Factor Tester

1

Use conditions

-15℃∽40℃

RH80%

2

Anti-interference

Frequency conversion

3

Power

AC 220V±10%


4

High output

0.5KV∽10KV

Every 0.1kV

Precision

2%

Maximum current  

200mA

Capacity

2000VA

5

Self-excited power

AC 0V∽50V/15A

45HZ/55HZ 47.5HZ/52.5HZ

55HZ/65HZ 57.5HZ/62.5HZ

Automatic double frequency

6

Resolving power

tgδ: 0.001%

Cx: 0.001pF

7

Precision

△tgδ:±(Reading*1.0%+0.040%)

△C x :±(Reading*1.0%+1.00PF)

8

measuring range

tgδ

Unlimited

C x

15pF < Cx < 300nF


10KV

Cx < 60  nF


 5KV

Cx < 150 nF


 1KV

Cx < 300 nF

CVT test

Cx < 300 nF

9

CVT range

10∽10000

accuracy

0.1%

Resolving power

0.01

10

Exterior dimension

350L×270W×270H

11

Memory size

The 200 group supports U disk data storage

12

Weight

28 Kg



Benefits:


  • Our GDGS uses the complex current method to measure capacitance, dielectric loss and other parameters. The test result has high accuracy, which is convenient for automatic measurement.

  • GDGS uses a large-screen LCD display, and the test process is prompted by the English menu, which is intuitive and easy to operate.

  • GDGS is an integrated model, with standard capacitors and high-voltage power supply, is convenient for on-site testing and reduces on-site wiring.

  • Grounding protection function. When the instrument is not grounded or grounded, the instrument will not enter the normal program and will not output high voltage. Over-current protection function, the instrument will not be damaged when the sample is short-circuited or broken down.

  • GDGS is always in stock. We can delivery it immediately after inspection.

GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester 02


GDGS Automatic Transformer Power Factor Tester, Transformer Tan Delta Tester 05


CVT Test

修改

Product Inquiry

QUICK LINK

CONTACT US

Tel : 0086-23-62613622
Phone : 0086-15123029885
Add : 25F, Huarun Center, Xiejiawan Street, Jiulongpo District, Chongqing, China, 400050
E-mail : gold06@hy-industry.com
Fax : 0086-23-62940030
Skype : christinejinhua@outlook.com

Whatsapp : +8615123029885
Wechat : + 8615123029885
Copyright  Chongqing Gold Mechanical&Electrical Equipment Co.,Ltd. All rights reserved. Site Map
公安备案号 50010802002590