Portable PD Tester with High Frequency Transformer for Power Cables Partial Discharge Test

Product Description

Portable PD Tester with High Frequency Transformer for Power Cables Partial Discharge Test






How to use GDJF-4 Portable PD Tester with High Frequency Transformer (HFCT)to detect partial discharge in cables?

Due to the special structure of cables, ultrasonic and high-frequency signals cannot be obtained from the outer layer of metal armor, so we can obtain signals from the grounding wire.


When partial discharge occurs inside the cable, high-frequency current will be guided along the grounding wire to the ground,Partial discharge detection achieved by installing high-frequency transformer on the ground wire to detect high-frequency current signals.There is no electrical connection between the measuring

circuit and the tested circuit of the high-frequency transformer, which belongs to non-invasive detection. Therefore, the equipment does not need to be shut down during high-frequency transformer detection.

Firstly, clamp the high-frequency transformer at the cablegrounding wire, and then connect the PD tester for reading and saving.

Horizontal comparison of partial discharge signals of the same type of equipment. The partial discharge signals detected by similar equipment in similar environments should have similar test amplitudes and test spectrum.

Secondly, vertical comparison of historical data of the same equipment. By measuring the partial discharge signal of the same equipment multiple times over a long period of time, the insulation status and degradation trend of the equipment can be tracked.

If there is a significant increase in the measured value or a typical partial discharge pattern appears, it can be determined that there is an abnormality within this test point.If a signal with discharge characteristics is detected, with a small test value and a large number of pulses, it is a typical interference signal.If the test value is large and the number of pulses is small, it is a typical discharge signal.



Main Application Scenarios:

1) On site inspection and status monitoring: Conduct rapid and regular screening of power equipment such as switchgear, transformers, and cable joints in operation (equipped with different sensors).

2) Preliminary fault diagnosis: After discovering abnormal signals, make preliminary judgments and trend analysis.

3) Emergency investigation: After equipment failure, quickly locate suspicious partial discharge sources.


Technical Index


TEV Measurement

Measuring range

0~70 dBmV

Resolution

1dB

Precision

±1dB

Maximum pulse per cycle

1400

Measurement frequency band

3~100MHz

AE measurement

Measuring range

-7~ 70dBμV

Resolution

1dB
Precision ±1dB

Frequency Range

20~200 kHz

AA Measurement
Measuring range

-7~70dBμV

Resolution

1dB

Precision

±1dB

Sensor center frequency

40 kHz

UHF measurement

Detection frequency

300-2000MHz

Measuring range 0-70 dBmV

Sensitivity

<1dBm

Sensor frequency band

300-3000MHz

HFCT measurement

Sensor transmission impedance

9.9mV/mA

Detection frequency

1~50MHz

Hardware

Shell

ABS

Screen

4.0 inch RGB LCD screen, resolution 800*480

Sampling accuracy

12bit

Connector

USB interface (also charger input)

3.5mm stereo headphone jack

External sensor input interface

Earphone

8 Ω minimum

Built-in battery

3.7V/5000mAh lithium battery


Our Partners


Product Inquiry