GDRZ-902 SFRA
CHONGQING GOLD
After a transformer has undergone short-circuit impacts, long-distance transportation and relocation, and major overhaul disassembly and assembly, the windings may shift or deform due to compression. Many routine test readings may still be within acceptable limits, but the internal mechanical structure of the windings has already been damaged, creating potential future faults. Frequency sweep response analysis is an effective means of detecting these mechanical defects.
However, field operations often encounter practical obstacles: electromagnetic interference and improper wiring processes cause curve spikes and abnormal shapes, making it impossible to determine whether they are actual equipment defects or errors introduced by the test; test files collected in different years have inconsistent formats, making it difficult to compare baseline data from many years ago with current field results; only images are saved after testing, and all original sampling points are lost, making in-depth comparison impossible later; after the test, the curves must be manually processed, correlation coefficients calculated, and report generation time-consuming.
| GDRZ-902 Transformer Winding Deformation Tester addresses this by ensuring the reliability of test data and allowing for long-term reuse of test archives for overall machine design. The instrument is compatible with both the domestic DL/T911-2016 and the corresponding IEC GB/T1094.18-2018 test procedures, and supports various winding connection methods. It can perform basic correlation analysis on the instrument itself, and can also export all original sampling points to computer software for multi-set horizontal and vertical comparisons. It outputs complete amplitude-frequency and phase-frequency curves, meeting the needs of factory handover, post-short-circuit fault assessment, and periodic inspection record retention. The lightweight enclosure facilitates transportation between substations and transformer manufacturers. |
Two complete frequency sweep schemes can be switched as needed. It adapts to the 10Hz-1MHz linear interval sweep of DL/T911-2016; it can also enable the segmented sweep mode of GB/T1094.18-2018, covering a maximum frequency band of 10MHz. The segmented mode uses differentiated step sizes for low, medium, and high frequencies, with encrypted sampling in the high-frequency band to reduce curve misjudgment caused by high-frequency signal loss. It also supports custom single-point frequency verification, allowing for targeted retesting and verification of abnormal frequency points in historical reports.
The instrument panel directly prints wiring diagrams for both DL/T and GB/T standards, corresponding to different connection methods for 50Ω matching impedances. The instrument comes with a complete set of BNC tees and shielded coaxial test cables, providing wiring instructions for Yn, Y, Δ, and Z type (zigzag winding) three-phase and single-phase transformers. The on-screen wiring prompt interface reduces the frequency of personnel consulting paper manuals and minimizes invalid tests caused by incorrect excitation or response connections.
The instrument can store up to 40 complete test files, which not only store curve screenshots but also the original dB amplitude and phase values for each frequency point. It supports on-screen playback and on-site thermal printing. Data can be uploaded to computer software via USB, allowing for horizontal comparison of multiple original datasets, including factory baselines from previous years, pre-test records from previous years, and current on-site data, rather than just static images.
After completing the three-phase test, the instrument directly provides correlation R coefficients for low, medium, and high frequency bands, quickly providing a preliminary reference for the winding status. For more rigorous archiving and evaluation, all raw data can be uploaded to the accompanying computer software. The software supports multi-file loading, curve overlay, and segmented correlation calculation, directly generating a complete test report in Word format, saving significant time spent on manual data transcription and calculation.
It outputs a 20Vpp low-voltage excitation signal; the hardware supports two sets of input impedances: 1MΩ (DL/T mode) and 50Ω (GB/T mode), strictly matching two sets of standard hardware conditions. During testing, both amplitude and phase frequency information are collected simultaneously. The phase curve can assist in troubleshooting: whether curve anomalies originate from external wiring interference or mechanical changes in the winding itself, providing engineers with more auxiliary judgment criteria.
The entire unit weighs less than 8kg, with a portable protective case. The screen supports Chinese and English switching; the system time is calibrable, and each stored file has its own time stamp; printer density and screen brightness can be adjusted on-site to adapt to different working light conditions in substations, including strong and low light.
Item | Specification |
|---|---|
Model | GDRZ‑902 |
Sweep Frequency Range | 10Hz‑1MHz(DL/T911‑2016);10Hz‑10MHz(GB/T1094.18‑2018 segmented) |
Amplitude Measuring Range | -100dB ~ +20dB |
Amplitude Accuracy | -40~+20dB:±0.2dB;‑60~‑40dB:±0.5dB;‑80~‑60dB:±1.0dB |
Phase Measuring Range | -180°~+180°(10Hz‑2MHz) |
Frequency Sweep Accuracy | <0.01% |
Input Impedance | >1MΩ(DL/T mode);50Ω(GB/T1094.18‑2018 mode) |
Output Impedance | 50Ω |
Max Output Voltage | 20Vpp |
Repeatability of same‑phase test | 99.5% |
Local Memory | Max.40 groups complete raw test datasets |
Power Supply | AC220V±10%,45‑65Hz |
Power Consumption | ≤60W |
Operation Ambient | 0‑50℃,RH ≤90% non‑condensing |
Dimension(L×W×H) | 400 mm ×400 mm ×190 mm |
Net Weight | <8kg |
1.Q: What are the practical advantages of GB/T segmented scanning mode compared to ordinary linear scanning?
A: Segmented mode uses smaller step sizes at low frequencies to ensure detail, and densifies sampling points at high frequencies. Many transformer winding defects manifest at high-frequency resonant points; segmented mode reduces the risk of missing key high-frequency information, making it suitable for in-depth fault assessment.
2.Q: Is simply printing a paper report sufficient for preserving test data?
A: Not recommended. Paper printouts only contain curve images; the instrument preserves the original frequency dataset. Subsequent retests over many years allow for comparison of the old and new sets of original data on computer software. Image files cannot perform this kind of refined secondary analysis.
3.Q: What role does the phase curve play in field testing?
A: If the amplitude-frequency curve is abnormal, the phase curve can help distinguish whether the problem originates from wiring, field interference, or changes in the winding's mechanical structure, providing engineers with an additional layer of diagnostic information.
4.Q: Without the original factory baseline, is SFRA testing still valuable?
A: It is possible to make a horizontal comparison between the three phases, using the A/B/C three-phase curves of the same transformer as a reference for comparison. However, the judgment conditions for horizontal comparison are different from those for baseline comparison, and the interpretation logic given in the standard must be strictly followed.